E-stops
Two-channel E-stop stations at operator positions, transfers, and access points, monitored by a safety relay or safety PLC.
Conveyor safety
E-stops, pull cords, guard interlocks, and safe removal of MDR motor power. Unless your risk assessment or company standard says otherwise, we design MDR conveyor safety functions to SIL 2 / PL d and verify them before handover.
Most MDR conveyor hazards are pinch points, nip points at transfers, and unexpected start-up. For these, a two-channel design (Category 3) reaching PL d under ISO 13849-1, or SIL 2 under IEC 62061, is a common and defensible target. We use it as the starting point.
The required level still comes from the risk assessment. If yours sets a different Performance Level, or your company standard does, we design to that instead. If there is no risk assessment yet, we can help you work through one.
A level is only claimed once it has been calculated with the real components and tested.
Safety functions
Each safety function is listed with its trigger, its stop zone, its target level, and how it will be tested.
Two-channel E-stop stations at operator positions, transfers, and access points, monitored by a safety relay or safety PLC.
Two-channel pull-cord switches along long runs where an operator can reach the conveyor, with cord tension and switch spacing per the manufacturer.
Interlocked guards and gates at transfers, lifts, and drive areas, with locking where run-down time requires it.
MDR motor power removed through redundant contactors with feedback monitoring (EDM), or a safety-rated input where the MDR platform provides one.
Stops grouped into zones that match the risk assessment, so one E-stop stops the hazard without shutting down the whole building.
Horns and beacons before motion where ASME B20.1 calls for them, such as when the whole conveyor can’t be seen from the start point.
Safety standard for conveyors and related equipment: guarding, emergency stops, and start-up warnings.
Safety-related parts of control systems. Performance Level (PL) and SIL are calculated from architecture, diagnostic coverage, and component reliability data.
Risk assessment principles that set the required level for each safety function.
Electrical standard for industrial machinery, including stop categories and control circuits.
Lockout/tagout: energy isolation points laid out and labeled for service work.
Verification
Paperwork and testing are part of the safety design, not an afterthought.
Every function listed with its input devices, logic, output devices, stop category, stop zone, and target level.
PL or SIL calculated with SISTEMA (ISO 13849-1) or to IEC 62061 using manufacturer data for each device, including contactor B10d values and switching rates.
At FAT and on site we test single faults: an opened channel, a welded contactor simulated through EDM, a cross-fault where the device detects it.
Test results recorded for each function and included in the closeout package, with the calculation report.
Anything we can’t verify, such as a customer-supplied device without safety data, is listed as an open item, not assumed.
Your inputs
Your existing risk assessment, or time with your safety lead to build one for the conveyor.
Any internal safety standard, preferred safety PLC or relay, and approved E-stop and pull-cord hardware.
Other equipment on the safety circuit: lifts, robots, palletizers, doors, or fire system inputs.
Next step
Send the layout, your risk assessment if you have one, and what the safety circuit looks like today. We’ll reply with questions and a scope.
Mon–Fri, 9:00 AM – 4:00 PM ET · we reply within one business day
Engineering offices in Clearwater, Florida · available for Zoom meetings